The explosion-proof AC mobile substation for mining is the mobile complete device consisting of the dry transformer for explosion-proof AC mobile substation for mining, permanent-magnet high-voltage vacuum switch for KBG series explosion-proof AC mobile substation for mining and low-voltage protection box for BXB series explosion-proof mobile substation for mining. It is applicable for the place with west environment under the coal mine, including gas and coal dust, and with explosion hazard, and provides power supply for the frequency inverter.
Model meaning:
Technical parameters:
Performance parameters of dry transformer for explosion-proof AC mobile substation for mining with primary rated voltage of 6kV
Rated capacity (kVA) |
Voltage combination (kV) |
Connection unit symbol |
Loss |
Impedance voltage (%) |
No-load current (%) |
||
Primary voltage |
Secondary voltage |
No load |
Load |
||||
1250 |
6 |
2×1.905 |
Dy11d0 |
3100 |
7400 |
8 |
1.1 |
1600 |
3680 |
8950 |
8 |
1 |
|||
2000 |
4180 |
10600 |
8 |
1 |
|||
2500 |
5100 |
12200 |
8 |
0.8 |
|||
3150 |
6800 |
13500 |
8 |
0.8 |
Performance parameters of dry transformer for explosion-proof AC mobile substation for mining with primary rated voltage of 10kV
Rated capacity (kVA) |
Voltage combination (kV) |
Connection unit symbol |
Loss |
Impedance voltage (%) |
No-load current (%) |
||
Primary voltage |
Secondary voltage |
No load |
Load |
||||
1250 |
10 |
2×1.905 |
Dy11d0 |
3400 |
8380 |
8 |
1.1 |
1600 |
3950 |
9750 |
8 |
1 |
|||
2000 |
4680 |
11200 |
8 |
1 |
|||
2500 |
5400 |
12400 |
8 |
0.8 |
|||
3150 |
7000 |
13700 |
8 |
0.8 |
Serial No. |
Model |
Length |
Width |
Height |
Weight |
Model |
Length |
Width |
Height |
Weight |
1 |
KBZSGZY-1250/6/2×1.905 |
4862 |
1055 |
1605 |
8890 |
KBZSGZY-1250/10/2×1.905 |
4862 |
1040 |
1650 |
8695 |
2 |
KBZSGZY-1600/6/2×1.905 |
4932 |
1060 |
1690 |
9675 |
KBZSGZY-1600/10/2×1.905 |
4932 |
1100 |
1705 |
9185 |
3 |
KBZSGZY-2000/6/2×1.905 |
5022 |
1110 |
1795 |
10950 |
KBZSGZY-2000/10/2×1.905 |
5012 |
1100 |
1865 |
11000 |
4 |
KBZSGZY-2500/6/2×1.905 |
5252 |
1160 |
1855 |
12670 |
KBZSGZY-2500/10/2×1.905 |
5222 |
1180 |
1920 |
12805 |
5 |
KBZSGZY-3150/6/2×1.905 |
5782 |
1270 |
1920 |
15765 |
KBZSGZY-3150/10/2×1.905 |
5952 |
1290 |
1920 |
16025 |
1. Low no-load loss
The high-quality cold rolled grain-oriented silicon steel sheet with high permeability and low loss is adopted for manufacturing. 45° fully-beveled seam and multi-stage step stacking structure, which effectively reduces no-load loss, no-load current and noise.
2. Low noise
The noise is from the iron core, and is transferred to the surrounding through the shell. The connecting position is added with silica gel plate, which cuts off the noise spreading approach.
3. Light weight and small volume
4. The converter mobile substation has explosion-proof and damp-proof performance.
5. The converter mobile substation has perfect overload, short circuit and leakage protection. There is electrical interlock or mechanical interlock device between the high- and low-voltage switches and the high-voltage switch and the circuit breaker of the upper stage.
6. Energy conservation and environmental protection
1) Nomex paper-wrapped line with insulation grade C imported from American DuPont Company is adopted, air insulation and cooling. It has no pollution on the environment, and the product has long service life; the product can be decomposed for recovery after the service life is ended;
2) The high-quality 30Q130 cold-rolled oriented silicon steel sheet and oxygen-free copper conductor are adopted, so that the actual total loss is lower than that of the foreign similar products, which saves the energy, and lowers noise. The iron core surface is applied with the high-temperature-resistant rust-proof and damp-proof paint, Grade H insulation material is adopted for the iron core insulator, and there is no damage after operation at high temperature for a long term.
©1996-2017 晋ICP备07500050号 Huaxin Copyright
©2016-2017 晋ICP备07500050号 Huaxin Copyright